ModelsDL-100T485/DL-100T485-WDL-100TM485/DL-100TM485-WDL-100T485P/DL-100T485P-WDL-100TM485P/DL-100TM485P-W
Temperature Sensor
Measuring Range-20 ~ +60°C (-31 ~ +176°F)
Resolution0.1°C
AccuracyTypical: ±0.4°C; refer to figure 2 for detailsTypical: ±0.3°C; refer to figure 2 for details
Humidity Sensor
Measuring Range0 ~ 100% RH
Resolution0.1% RH
AccuracyTypical: ±3% RH @ 20 ~ 80% RH; refer to figure 1 for detailsTypical: ±1.8% RH @ 10 ~ 90% RH; refer to figure 1 for details
LCD Display
Displayed InformationTemperature (°C and °F), Humidity (RH), Module ID
Data Logger
Time Interval10 seconds to 1 day
Max. Records4088 temperature and humidity records
ModeOverwrite or stop logging when storage space is full
Overwrite Limitation1,000,000 cycles
Communication
InterfaceRS-485; non-isolated
Baudrate1200 ~ bps
Data formatN,8,1
ProtocolDCONModbus RTUDCONModbus RTU
Max. Modules on same bus32
Power
Input Range+10 ~ +30 VDC
Power Consumption0.15 W
Mechanical
Dimensions (W x L x H)82 mm x 126 mm x 55 mm
Waterproof LevelIP66
InstallationDIN-Rail; Wall mount
Environment
Operating Temperature-20 ~ +60°C
Storage Temperature-30 ~ +80°C
Ambient Relative Humidity5 ~ 95% RH, Non-condensing